LCN-PKE Issendorff KG
499,99 €
precedentemente 499,99 €
Non più disponibile
Info sui prodotti "LCN-PKE Issendorff KG"
Coupling Module for Connecting to a Network
The LCN-PKE is a network coupler for the LCN bus. Communication occurs via LAN with RJ45 or WLAN. The coupler includes the LCN-PCHK service. It is compatible with all LCN bus modules from firmware 0701... (January 1997).
Application Areas
Typical application areas of the LCN-PKE include:
- Remote maintenance with LCN-PRO
- Visualization with LCN-GVS
- Coupling with PCK protocol
The LCN-PKE serves as a network access point to the LCN system. Through this access, the parameterization of the LCN system is performed by the installer or coupled with other systems across trades.
Another application case is the connection of the LCN visualization on the PC. Using the system software LCN-GVS, direct and bidirectional data exchange between LCN system states and direct control commands from the visualization PC occurs.
Hardware Features
- RJ-45 interface
- WLAN interface
- Connection to the LCN bus
- Optical status display of the operating state
Note: It is not possible to access the LCN-PKE with two LCN-PRO of the same license.
Function Description
The LCN-PKE supports two simultaneous PCHK connections to the LCN bus, allowing both LCN-GVS and LCN-PRO to access the bus simultaneously. The PCHK monitor under Windows serves optionally for further configuration and monitoring of the LCN-PKE. For the third connection to the LCN bus, a full version LCN-PCHK license must be entered via the PCHK monitor. Each additional connection requires an upgrade license.
Coupling LCN-PCK
To get data from a third-party application onto the LCN bus via LCN-PCK, this software is required. It buffers incoming and outgoing commands and messages, checks and translates them.
The communication connection uses the TCP/IP network. This protocol works with simple ASCII strings. An example: M000111A1100010 means module 111 in segment 000, output 1 to 100 with ramp 10. Feedback such as status or measured values are returned similarly simple and logically. This type of communication is fast and easy to implement in third-party applications.
Date/Time
With an existing internet connection, the LCN-PKE regularly resets the time. Thus, all LCN modules have the current time, which can be displayed on an LCN-GT4D/-GT10D. This function can be configured via the PKE web interface.
Technical Data
- Connection
- Supply voltage: 85V - 265V, 50/60 Hz
- Power consumption: 2 W
- Terminals/wire type: screwless, solid max. 2.5 mm² or stranded with end sleeve max 1.5 mm², through-wiring current max. 16 A
- Connection to the Network
- LAN: RJ45
- WLAN: 802.11b/g/n, WPA2 encrypted
- Installation
- Operating temperature: -10 to 40 °C
- Humidity: Max. 80% rel., non-condensing
- Environmental conditions: Use in fixed installations according to VDE 632, VDE 637
- Protection class: IP20
The LCN-PKE galvanically isolates the LCN bus up to 4 kV from the RJ45 socket.
Note: Only limited quantities available. LCN-PKE is being replaced by LCN-Visu.